CALCULATOR · VALVES
Control valve Cv and Kv for liquids
Required flow coefficient for a liquid duty, with a choked-flow and flashing check, using the IEC 60534-2-1 liquid equations. Results update as you type.
Water: 0 to 150 °C.
Filled in for water.
At the inlet temperature. Filled in for water.
Water: 220.64. Used only for the choked-flow limit.
Check the maximum, normal and minimum flows in turn.
Gauge units assume sea-level air pressure.
From the vendor. Globe valves are often about 0.9; ball and butterfly valves lower, often about 0.55 to 0.75.
Full-open Cv from the vendor’s table. Leave empty to skip.
Valve the same size as the pipe (no reducers). Preliminary sizing only; confirm with the vendor’s sizing program.
How the calculator works
A valve’s flow coefficient says how much liquid it passes for a given pressure drop. Kv is the flow of water in m³/h at 1 bar drop; Cv is the flow of water in US gallons per minute at 1 psi drop. Cv = 1.156 × Kv.
- Required Kv: Kv = Q × √(SG / Δp), with Q in m³/h, Δp in bar and SG the liquid density divided by that of water at 15 °C (999.1 kg/m³).
- Choked-flow limit: Δpmax = FL² × (P1 − FF × Pv), with FF = 0.96 − 0.28 × √(Pv / Pc). Beyond this drop, more pressure drop gives no more flow.
- Sizing drop: the smaller of the actual drop and Δpmax.
- Flashing: if the outlet pressure is below the vapour pressure, part of the liquid stays as vapour after the valve.
The calculator assumes the valve is the same size as the pipe. Reducers on each side add a piping geometry factor FP below 1, which the vendor’s program will include.
Worked example
Water at 20 °C, 50 m³/h, inlet 6 bar g, outlet 4 bar g, a globe valve with FL = 0.9 and a rated Cv of 63:
| Step | Calculation | Result |
|---|---|---|
| Pressures | P1 = 7.013 bar abs, P2 = 5.013 bar abs, Δp = 2.0 bar | – |
| Relative density | 998.2 / 999.1 | 0.999 |
| Choked-flow limit | 0.9² × (7.013 − 0.957 × 0.023) | 5.66 bar (not choked) |
| Required Kv | 50 × √(0.999 / 2.0) | 35.3 |
| Required Cv | 1.156 × 35.3 | 40.9 |
| Share of rated Cv | 40.9 / 63 | 65% |
Check: 100 US gpm of water across 25 psi gives Cv = 100 × √(1 / 25) = 20, and the calculator returns 20.0 for that case.
Things that change the answer
- The whole flow range: size at maximum flow and check that minimum flow still sits well above the bottom of the valve’s travel.
- Hot water and light liquids: high vapour pressure lowers the choked-flow limit. Water at 90 °C across a 2.8 bar drop is already choked with FL = 0.9.
- Cavitation: damage can begin before flow chokes. For large drops on hot or volatile liquids, ask for the vendor’s cavitation assessment.
- Viscous liquids: at low Reynolds numbers the valve passes less than the formula says. IEC 60534-2-1 adds a correction for this.
Related tools: Pipe Pressure Drop Calculator and Pump Power Calculator.