CALCULATOR · PUMPS
Pump affinity laws
How flow, head and power change when you change a centrifugal pump’s speed or trim its impeller. Results update as you type.
From the pump curve, or from the pump power calculator.
These points slide along the pump curve.
How the calculator works
For a centrifugal pump, each point on the curve moves in a fixed way when the speed changes. With r = N2 / N1:
- Flow: Q2 = Q1 × r
- Head: H2 = H1 × r²
- Power: P2 = P1 × r³ (efficiency stays about the same)
Trimming the impeller at constant speed follows the same pattern with r = D2 / D1, as long as the trim is small. NPSH required also falls at lower speed, roughly with r², but check the vendor’s curve.
Worked example
A pump delivers 100 m³/h at 50 m head and takes 19.42 kW at 2,950 rpm. A VFD slows it to 2,400 rpm:
| Step | Calculation | Result |
|---|---|---|
| Speed ratio | 2,400 / 2,950 | 0.814 |
| New flow | 100 × 0.814 | 81.4 m³/h |
| New head | 50 × 0.814² | 33.1 m |
| New shaft power | 19.42 × 0.814³ | 10.46 kW (46% less) |
A 19% cut in speed nearly halves the power. That cube law is why VFDs pay back so well on pumps and fans, but only where the system lets the speed come down.
Things that change the answer
- Static head: the laws move a point along the pump curve, not along your system curve. If the system has a lot of static head, slowing the pump cuts flow much faster than r, and too low a speed delivers nothing.
- Big trims: beyond about 10 to 15% off the diameter, efficiency drops and the simple laws overstate the flow and head.
- Minimum flow: at low speed the pump may run below its minimum continuous flow. Check the vendor’s limit.
- Motor and VFD losses: the electrical saving is a little less than the shaft-power saving.
Related tools: Pump Power Calculator and NPSH Calculator.