NPSH Calculator

CALCULATOR · PUMPS

NPSH available and margin

NPSH available from the suction tank, the suction pipe and the liquid, then the margin over the pump’s NPSH required. Results update as you type.

Use the highest operating temperature. Water: 0 to 150 °C.

Filled in for water.

At the highest temperature. Filled in for water.

Filled in for water.

Open tank: local air pressure, 101.3 kPa at sea level, about 89.9 kPa at 1,000 m. bar g assumes sea level.

Minimum level. Negative if the liquid is below the pump (suction lift).

Highest flow, not only the rated flow.

DN100 Sch 40: 102.3. DN150 Sch 40: 154.1.

Commercial steel: 0.045. Plastic pipe: about 0.0015 to 0.007.

Tank entrance 0.5, long-radius elbow 0.2, full-port ball valve 0.05, clean strainer about 1 to 2 (ask the vendor).

From the pump curve at the highest flow. Leave empty to skip the margin.

NPSH AVAILABLE–
MARGIN (NPSHA − NPSHR)–
MARGIN RATIO (NPSHA / NPSHR)–
SURFACE PRESSURE HEAD–
VAPOUR PRESSURE HEAD–
SUCTION LINE LOSS–
VELOCITY IN SUCTION PIPE–
FRICTION FACTOR–

Preliminary check only. Use the minimum liquid level, the highest temperature and the highest flow.

How the calculator works

NPSH available is the pressure the liquid has at the pump suction, above its own vapour pressure, written as metres of that liquid. If it falls too low, vapour bubbles form in the impeller eye and collapse further in: that is cavitation.

  • NPSHa = hp + hz − hvp − hf
  • Surface pressure head: hp = Pabs / (ρ × g), with g = 9.80665 m/s².
  • Static head: hz is the minimum liquid level above the pump centreline (negative for suction lift).
  • Vapour pressure head: hvp = Pv / (ρ × g) at the highest temperature.
  • Suction line loss: hf = (f × L / D + ΣK) × v² / (2g). The friction factor f comes from the Colebrook equation (64 / Re in laminar flow).

For water, the calculator fills in the properties: vapour pressure from the IAPWS-IF97 saturation equation, density from Kell’s equation and viscosity from a Vogel-type fit.

Worked example

Condensate at 85 °C drawn from a vented tank at sea level, minimum level 3.2 m above the pump centreline, 45 m³/h through 8.5 m of DN100 Sch 40 steel pipe (inside diameter 102.3 mm) with fittings adding up to K = 2.30. The pump curve gives NPSH3 = 4.8 m at that flow.

StepCalculationResult
Water at 85 °Cρ = 968.6 kg/m³, Pv = 57.87 kPa abs, μ = 0.330 mPa·s–
Velocity0.0125 m³/s / 0.00822 m²1.52 m/s
Friction factorRe ≈ 457,000, ε/D = 0.00044, Colebrook0.0174
Suction line loss(0.0174 × 8.5 / 0.1023 + 2.30) × 0.118 m0.44 m
Surface pressure head101,325 / (968.6 × 9.80665)10.67 m
Vapour pressure head57,870 / (968.6 × 9.80665)6.09 m
NPSH available10.67 + 3.20 − 6.09 − 0.447.33 m
Margin and ratio7.33 − 4.80; 7.33 / 4.802.53 m; 1.53

The same example is worked by hand in the NPSH guide.

Things that change the answer

  • Temperature: vapour pressure climbs fast as liquid gets hot. A few degrees can take metres off NPSH available near the boiling point.
  • Highest flow: line losses grow with the square of the flow, and NPSH required rises too. Check at run-out, not only at the rated point.
  • Altitude and vacuum: an open tank high above sea level, or a vessel under vacuum, has less surface pressure to work with.
  • Strainers: a part-blocked strainer can add more loss than the rest of the line. Allow for it at the alarm differential pressure.
  • Margin: NPSH3 is the point where the pump has already lost 3% of its head. ANSI/HI 9.6.1 sets a minimum margin above it for each service, and it is always above 1.0.

Related tool: Pump Power Calculator.

Need a second opinion on a suction system? Talk to Avoltium about a one-hour expert call.